Table No. 1
Plain Copper Conductor, PVC Insulated UNsheathed 650/1100 V, SINGLE CORE CABLES
FOR PANEL BOARD WIRING As per is:694/1990 with isi Mark (UP TO 50 SQ. MM)
Area in
Sq. mm |
Conductor
Construc-
tion in
General |
Cond.
Dia.
in mm |
Max. DC
Resistance
Ohm/Km
At 20°C |
Insulation
Thickness
in mm
Nominal |
Cables
Dia
(Approx.) |
Current
Rating
in Amp. |
Area in
Sq. mm |
Conductor
Construc-
tion in
General |
Conductor
Dia.
In mm |
Max DC
Resistance
Ohm/Km
At 20°C |
Insulation
Thickness
in mm
Nominal |
Cable
Dia
(Approx.) |
Cable
Dia
(Approx.) |
0.50 |
16/0.20 |
0.94 |
39.00
|
0.60 |
2.20 |
4
|
70
|
360/0.50 |
12.30 |
0.272 |
1.6 |
15.5
|
170 |
0.75 |
24/0.20 |
1.20
|
26.00 |
0.60 |
2.50 |
7 |
95 |
485/0.50 |
14.70 |
0.206 |
1.8 |
18.5 |
210 |
1.00 |
32/0.20 |
1.34 |
19.50 |
0.60 |
2.60 |
11 |
120 |
608/0.50 |
16.70 |
0.161 |
2.0 |
20.9 |
235 |
1.50 |
*30/0.25 |
1.64 |
13.30 |
0.60 |
2.90 |
14 |
150 |
750/0.50 |
18.30 |
0.129 |
2.0 |
22.5 |
295 |
2.50 |
**50/0.25 |
2.08 |
7.98 |
0.70 |
3.50 |
19 |
185 |
925/0.50 |
20.00 |
0.106 |
2.2 |
24.6 |
330 |
4.00 |
56/0.30 |
2.61 |
4.95 |
0.80 |
4.30 |
26 |
240 |
1221/0.50 |
23.00 |
0.0801 |
2.2 |
27.6 |
400 |
6.00 |
84/0.30 |
3.50 |
3.300 |
0.80 |
5.30 |
33 |
300 |
1527/0.50 |
27.20 |
0.0641 |
2.4 |
32.2 |
475 |
10.00 |
140/0.30 |
4.60 |
1.910 |
1.00 |
6.70 |
45 |
400 |
2036/0.50 |
30.50 |
0.0486 |
2.6 |
35.7 |
550 |
16.00 |
126/0.40 |
6.00 |
1.210 |
1.00 |
8.20 |
60 |
500 |
2540/0.5 |
32.00 |
0.0384 |
2.8 |
38.0 |
635 |
25.00 |
196/0.40 |
7.60 |
0.780 |
1.20 |
10.00 |
75 |
630 |
3200/0.5 |
39.00 |
0.0287 |
3.0 |
45.5 |
725 |
35.00 |
276/0.40 |
8.70 |
0.554 |
1.20 |
11.3 |
95 |
800 |
4100/0.5 |
44.00 |
0.0224 |
3.4 |
51.0 |
840 |
50.00 |
396/0.40 |
10.60 |
0.386 |
1.40 |
13.5 |
125 |
1000 |
5100/0.5 |
46.00 |
0.0178 |
3.4 |
53.0 |
950 |
NOTE : Cable above 50 Sq. mm are not covered by IS:694 But are as per IS-2465
* This size can be supplied in 48/0.2 construction.
* This size can be supplied in 80/0.2 construction
The above Data is Indicative and may be Revised Without prior Information
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
|
Table No. 2
Plain Copper Conductor, PVC Insulated and sheathed 650/1100 V,
Multicore Flexible Cables As per is:694/1990 with isi Mark
Area in
Sq. mm |
Area in
Sq. mm |
Construc-
tion
No./Dia |
Max. DC
resist-
ance
Ohm/Km
at 20°C |
Insulation
thickness
nominal
mm |
Core
dia.
mm |
Sheath thickness
in mm nominal |
Overall Diameter
in mm approx. |
Current
Rating
Amp. |
2 core |
3 core |
4 core |
2 core |
3core |
4 core |
0.50
|
16/0.2
|
0.94
|
39.00
|
0.60 |
2.20 |
0.90 |
0.90 |
0.90 |
6.20 |
6.60 |
7.20 |
4 |
0.75 |
24/0.2 |
1.20 |
26.00 |
0.60 |
2.50 |
0.90 |
0.90 |
0.90 |
6.80 |
7.20 |
7.90 |
7 |
1.00 |
32/0.2 |
1.34 |
19.50 |
0.60 |
2.60 |
0.90 |
0.90 |
0.90 |
7.00 |
7.50 |
8.10 |
11 |
1.50 |
*30/0.25 |
1.64 |
13.30 |
0.60 |
2.90 |
0.90 |
0.90 |
1.00 |
7.60 |
8.10 |
9.00 |
14 |
2.50 |
**50/0.25 |
2.08 |
7.98 |
0.70 |
3.50 |
1.00 |
1.00 |
1.00 |
9.00 |
9.60 |
10.50 |
19 |
4.00 |
56/0.3 |
2.61 |
4.95 |
0.80 |
4.30 |
1.00 |
1.00 |
1.00 |
10.60 |
11.30 |
12.40 |
26 |
* This size can be supplied in 48/0.2 construction.
* This size can be supplied in 80/0.2 construction
Table No. 3
Plain Copper Conductor, PVC Insulated and
sheathed 650/1100 V, Multicore Flexible Cables
|
Area in
Sq. mm |
Area in
Sq. mm |
Construc-
tion
No./Dia |
Max. DC
resist-
ance
Ohm/Km
at 20°C |
Insulation
thickness
nominal
mm |
Core
dia.
mm |
Sheath thickness
in mm nominal |
Overall Diameter
in mm approx. |
Current
Rating
Amp. |
2 core |
3 core |
4 core |
2 core |
3core |
4 core |
6
|
84/0.3 |
3.50
|
3.30
|
0.80
|
5.10
|
1.15 |
1.15
|
1.40 |
12.60
|
13.40 |
15.20
|
33 |
10 |
140/0.3 |
4.60 |
1.91 |
1.00 |
6.60 |
1.40 |
1.40 |
1.40 |
16.00 |
17.00 |
18.80 |
45 |
16 |
126/0.4 |
6.00 |
1.21 |
1.00 |
8.00 |
1.40 |
1.40 |
1.40 |
18.80 |
20.10 |
22.20 |
60 |
25 |
196/0.4 |
7.60 |
0.780 |
1.20 |
10.00 |
2.00 |
2.00 |
2.00 |
24.00 |
25.60 |
28.20 |
75 |
35 |
276/0.4 |
8.70 |
0.554 |
1.20 |
11.10 |
2.00 |
2.00 |
2.00 |
26.30 |
28.00 |
31.00 |
95 |
50 |
396/0.4 |
10.60 |
0.386 |
1.40 |
13.40 |
2.00 |
2.00 |
2.00 |
30.90 |
33.00 |
36.50 |
125 |
70 |
360/0.5 |
12.30 |
0.272 |
1.40 |
15.10 |
2.00 |
2.20 |
2.40 |
34.20 |
37.00 |
41.00 |
170 |
95 |
485/0.5 |
14.70 |
0.206 |
1.60 |
17.90 |
2.20 |
2.40 |
2.40 |
40.20 |
43.50 |
47.80 |
170 |
The above Data is Indicative and may be Revised Without prior Information
--------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
Table No. 4
Multicore Round Flexible Cable (6 Cores to 30 Cores)
Generlly as per Is : 694/1990
|
| Area Sq. mm |
0.50 |
0.75 |
1.00 |
1.50 |
2.50 |
4.00 |
General Constructionno./dia |
16/0.2 |
24/0.2 |
32/0.2 |
*30/0.25 |
**50/0.25 |
56/0.3 |
| Conductor Dia in MM |
0.94 |
1.20 |
1.34 |
1.64 |
2.08 |
2.61 |
| Avg. Insu. thickness in MM |
0.60 |
0.60 |
0.60 |
0.60 |
0.70 |
0.80 |
| Core Dia in MM |
2.20 |
2.50 |
2.60 |
2.90 |
3.50 |
4.30 |
No. of Cores :
|
6 |
Avg. Sheath thickness MM |
0.90 |
1.00 |
1.00 |
1.00 |
1.10 |
1.20 |
| App. Overall Dia MM |
8.50 |
9.50 |
9.80 |
10.70 |
12.70 |
15.30 |
7 |
Avg. Sheath thickness MM |
0.90 |
1.00 |
1.00 |
1.00 |
1.10 |
1.20 |
| App. Overall Dia MM |
8.50 |
9.50 |
9.80 |
10.70 |
12.70 |
15.30 |
8 |
Avg. Sheath thickness MM |
1.00 |
1.00 |
1.00 |
1.10 |
1.30 |
1.30 |
| App. Overall Dia MM |
9.30 |
10.40 |
10.70 |
11.90 |
14.10 |
16.90 |
10 |
Avg. Sheath thickness MM |
1.00 |
1.10 |
1.10 |
1.10 |
1.30 |
1.40 |
| App. Overall Dia MM |
10.80 |
12.20 |
12.60 |
13.80 |
16.60 |
20.00 |
12 |
Avg. Sheath thickness MM |
1.00 |
1.10 |
1.10 |
1.10 |
1.30 |
1.40 |
| App. Overall Dia MM |
11.20 |
12.60 |
13.00 |
14.30 |
17.20 |
20.70 |
14 |
Avg. Sheath thickness MM |
1.10 |
1.10 |
1.10 |
1.20 |
1.30 |
1.40 |
| App. Overall Dia MM |
12.00 |
13.30 |
13.70 |
15.20 |
18.10 |
21.80 |
16 |
Avg. Sheath thickness MM |
1.10 |
1.20 |
1.20 |
1.20 |
1.40 |
1.50 |
| App. Overall Dia MM |
12.60 |
14.20 |
14.60 |
16.00 |
19.30 |
23.20 |
19 |
Avg. Sheath thickness MM |
1.10 |
1.20 |
1.30 |
1.30 |
1.40 |
1.50 |
| App. Overall Dia MM |
13.20 |
14.90 |
15.60 |
17.10 |
20.30 |
24.50 |
24 |
Avg. Sheath thickness MM |
1.20 |
1.30 |
1.30 |
1.40 |
1.40 |
1.50 |
| App. Overall Dia MM |
15.60 |
17.60 |
18.20 |
20.20 |
23.80 |
28.80 |
30 |
Avg. Sheath thickness MM |
1.30 |
1.30 |
1.30 |
1.40 |
1.40 |
1.50 |
| App. Overall Dia MM |
16.80 |
18.70 |
19.30 |
21.50 |
25.70 |
30.60 |
| |
Max.ConductorResistanceinOHm/Km at20°C. |
39.00 |
26.00 |
19.50 |
13.30 |
7.98 |
4.95 |
| |
Recommended Current Rating in AMP |
4 |
7 |
11 |
14 |
19 |
26 |
* This size can be supplied in 48/0.2 construction.
* This size can be supplied in 80/0.2 construction
|
| --------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------- |
| Extra
High Voltage (EHV) |
1.1 kv Twin core, aluminium conductor, pvc insulated, inner sheathed,
armoured Pvc sheathed cables conforming to is: 1554 (part i) amended upto date |
Nominal
cross
Sectional
area
|
Nominal
Thickness
of
insulation
|
Minimum
thikness
of Inner
Sheth
|
ARMOUR |
Minimum
thikness
of outer
sheath
|
|
|
Max. DC
conductor
resistance
at 20° C G
|
|
Galv.
round
steel wire
Nominal
diameter
|
Galv.
flat
steel strip
Nominal
thikness
|
|
|
|
mm |
mm |
mm |
mm |
mm |
mm |
mm |
kg/km |
kg/km |
Amps. |
Amps. |
Amps. |
*1.5 |
0.8 |
0.3 |
1.4 |
— |
1.24 |
12.2 |
320 |
18.1000 |
18 |
16 |
16 |
*2.5 |
0.9 |
0.3 |
1.4 |
— |
1.24 |
13.4 |
380 |
12.1000 |
25 |
21 |
21 |
*4.0 |
1.0 |
0.3 |
1.4 |
— |
1.24 |
14.7 |
450 |
7.4100 |
32 |
27 |
27 |
*6.0 |
1.0 |
0.3 |
1.4 |
— |
1.24 |
15.8 |
500 |
4.6100 |
40 |
34 |
35 |
*10 |
1.0 |
0.3 |
1.4 |
— |
1.24 |
17.9 |
600 |
3.0800 |
55 |
45 |
47 |
16 |
1.0 |
0.3 |
— |
0.8 |
1.40 |
17.0 |
500 |
1.9100 |
70 |
58 |
59 |
25 |
1.2 |
0.3 |
— |
0.8 |
1.40 |
20.1 |
650 |
1.2000 |
90 |
76 |
78 |
35 |
1.2 |
0.3 |
— |
0.8 |
1.40 |
21.7 |
750 |
0.8680 |
110 |
92 |
99 |
50 |
1.4 |
0.3 |
— |
0.8 |
1.40 |
24.5 |
950 |
0.6410 |
135 |
115 |
125 |
70 |
1.4 |
0.3 |
— |
0.8 |
1.56 |
27.1 |
1150 |
0.4430 |
160 |
140 |
150 |
95 |
1.6 |
0.4 |
— |
0.8 |
1.56 |
30.8 |
1460 |
0.3200 |
190 |
170 |
185 |
120 |
1.6 |
0.4 |
— |
0.8 |
1.56 |
32.9 |
1670 |
0.2530 |
210 |
190 |
210 |
150 |
1.8 |
0.4 |
— |
0.8 |
1.72 |
36.3 |
2010 |
0.2060 |
240 |
210 |
240 |
185 |
2.0 |
0.5 |
— |
0.8 |
1.88 |
40.3 |
2450 |
0.1640 |
275 |
275 |
275 |
240 |
2.2 |
0.5 |
— |
0.8 |
2.04 |
44.8 |
2950 |
0.1250 |
320 |
275 |
325 |
300 |
2.4 |
0.6 |
— |
0.8 |
2.20 |
49.6 |
3560 |
0.1000 |
355 |
305 |
365 |
400 |
2.6 |
0.7 |
— |
0.8 |
2.36 |
55.9 |
4500 |
0.0778 |
385 |
345 |
420 |
500 |
3.0 |
0.7 |
— |
0.8 |
2.68 |
62.5 |
5600 |
0.0605 |
410 |
370 |
450 |
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
1.1 kv Three core, aluminium conductor, pvc insulated, inner sheathed,
armoured Pvc sheathed cables conforming to is: 1554 (part i) amended upto date |
*1.5 |
0.8 |
0.30 |
1.4 |
— |
1.24 |
12.7 |
375 |
18.1000 |
16 |
14 |
13 |
*2.5 |
0.9 |
0.30 |
1.4 |
— |
1.24 |
14.0 |
425 |
12.1000 |
21 |
18 |
18 |
*4.0 |
1.0 |
0.30 |
1.4 |
— |
1.24 |
15.6 |
500 |
7.4100 |
28 |
23 |
23 |
*6.0 |
1.0 |
0.30 |
1.4 |
— |
1.24 |
17.3 |
575 |
4.6100 |
35 |
30 |
30 |
*10 |
1.0 |
0.30 |
1.4 |
— |
1.40 |
19.0 |
700 |
3.0800 |
46 |
39 |
40 |
16 |
1.0 |
0.30 |
— |
0.8 |
1.40 |
19.3 |
650 |
1.9100 |
60 |
50 |
51 |
25 |
1.2 |
0.30 |
— |
0.8 |
1.40 |
22.0 |
800 |
1.2000 |
76 |
63 |
70 |
35 |
1.2 |
0.30 |
— |
0.8 |
1.40 |
24.0 |
950 |
0.8680 |
92 |
77 |
86 |
50 |
1.4 |
0.30 |
— |
0.8 |
1.56 |
27.6 |
1200 |
0.6410 |
110 |
95 |
105 |
70 |
1.4 |
0.40 |
— |
0.8 |
1.56 |
30.8 |
1500 |
0.4430 |
135 |
115 |
130 |
95 |
1.6 |
0.40 |
— |
0.8 |
1.56 |
34.6 |
1900 |
0.3200 |
165 |
140 |
155 |
120 |
1.6 |
0.50 |
— |
0.8 |
1.72 |
37.5 |
2240 |
0.2530 |
185 |
155 |
180 |
150 |
1.8 |
0.50 |
— |
0.8 |
1.88 |
41.9 |
2700 |
0.2060 |
210 |
175 |
205 |
185 |
2.0 |
0.60 |
— |
0.8 |
1.88 |
41.9 |
3200 |
0.1640 |
235 |
200 |
240 |
240 |
2.2 |
0.60 |
— |
0.8 |
2.20 |
41.9 |
3990 |
0.1250 |
275 |
235 |
280 |
300 |
2.4 |
0.70 |
— |
0.8 |
2.36 |
56.7 |
4850 |
0.1000 |
305 |
260 |
315 |
400 |
2.6 |
0.70 |
— |
0.8 |
2.52 |
56.7 |
6100 |
0.0778 |
335 |
290 |
375 |
500 |
3.0 |
0.7 |
— |
0.8 |
2.84 |
71.5 |
7600 |
0.0605 |
350 |
310 |
410 |
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
1.1 kv Four core, aluminium conductor, pvc insulated, inner sheathed,
armoured Pvc sheathed cables conforming to is: 1554 (part i) amended upto date |
*1.5 |
0.8 |
0.3 |
1.4 |
— |
1.24 |
15.0 |
400 |
18.1000 |
16 |
14 |
13 |
*2.5 |
0.9 |
0.3 |
1.4 |
— |
1.24 |
16.5 |
480 |
12.1000 |
21 |
18 |
18 |
*4.0 |
1.0 |
0.3 |
1.4 |
— |
1.24 |
18.0 |
550 |
7.4100 |
28 |
23 |
23 |
*6.0 |
1.0 |
0.3 |
1.4 |
— |
1.24 |
19.5 |
650 |
4.6100 |
35 |
30 |
30 |
*10 |
1.0 |
0.3 |
1.4 |
— |
1.40 |
20.0 |
660 |
3.0800 |
46 |
39 |
40 |
16 |
1.0 |
0.3 |
— |
0.8 |
1.40 |
23.0 |
750 |
1.9100 |
60 |
50 |
51 |
25 |
1.2 |
0.3 |
— |
0.8 |
1.40 |
23.7 |
950 |
1.2000 |
76 |
63 |
70 |
35 |
1.2 |
0.3 |
— |
0.8 |
1.40 |
25.9 |
1165 |
0.8680 |
92 |
77 |
86 |
50 |
1.4 |
|
— |
0.8 |
1.56 |
30.4 |
1540 |
0.6410 |
110 |
95 |
105 |
70 |
1.4 |
0.4 |
— |
0.8 |
1.56 |
33.5 |
1800 |
0.4430 |
135 |
115 |
130 |
95 |
1.6 |
0.4 |
— |
0.8 |
1.72 |
38.1 |
2400 |
0.3200 |
165 |
140 |
155 |
120 |
1.6 |
0.5 |
— |
0.8 |
1.88 |
41.9 |
2800 |
0.2530 |
185 |
155 |
180 |
150 |
1.8 |
0.5 |
— |
0.8 |
1.88 |
45.9 |
3350 |
0.2060 |
210 |
175 |
205 |
185 |
2.0 |
0.6 |
— |
0.8 |
2.04 |
50.9 |
4000 |
0.1640 |
235 |
200 |
240 |
240 |
2.2 |
0.6 |
— |
0.8 |
2.36 |
57.1 |
5050 |
0.1250 |
275 |
235 |
280 |
300 |
2.4 |
0.7 |
— |
0.8 |
2.54 |
63.2 |
6200 |
0.1000 |
305 |
260 |
315 |
400 |
2.6 |
0.7 |
— |
0.8 |
2.84 |
71.4 |
7850 |
0.0778 |
335 |
290 |
375 |
500 |
3.0 |
0.7 |
— |
0.8 |
3.00 |
79.2 |
9600 |
0.0605 |
350 |
310 |
410 |
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
1.1 kv 31/2 core, aluminium conductor, pvc insulated, inner sheathed,
armoured Pvc sheathed cables conforming to is: 1554 (part i) amended upto date |
Nominal cross
sectional area |
Nominal thickness
of insulation |
Minimum
thickness
of
inner
sheath |
Armour
Galv.
flat steel
strip
nominal
thickness |
Minimum
thinckness
of
outer
sheath |
Approx.
overall
diamete |
Approx.
weight
of
cable |
Max. DC conductor
resistance at 20° C |
Current Ratings |
| Main |
Neutral |
Main |
Neutral |
Main |
Neutral |
Driect in Ground |
In Ducts |
In Air |
| Sq. mm |
Sq. mm |
mm |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
Ohm/km |
Ohm/km |
Amps. |
Amps. |
Amps. |
| 25 |
16 |
1.2 |
1.0 |
0.3 |
0.8 |
1.40 |
23.1 |
900 |
1.200 |
1.910 |
76 |
63 |
70 |
| 35 |
16 |
1.2 |
1.0 |
0.3 |
0.8 |
1.40 |
24.9 |
1030 |
0.868 |
1.910 |
92 |
77 |
86 |
| 50 |
25 |
1.4 |
1.2 |
0.3 |
0.8 |
1.56 |
28.8 |
1350 |
0.641 |
1.200 |
100 |
95 |
105 |
| 70 |
35 |
1.4 |
1.2 |
0.3 |
0.8 |
1.56 |
32.2 |
1725 |
0.443 |
0.868 |
135 |
115 |
130 |
| 95 |
50 |
1.6 |
1.4 |
0.4 |
0.8 |
1.56 |
36.3 |
2130 |
0.320 |
0.641 |
165 |
140 |
155 |
| 120 |
70 |
1.6 |
1.4 |
0.5 |
0.8 |
1.72 |
40.1 |
2580 |
0.253 |
0.443 |
185 |
155 |
180 |
| 150 |
70 |
1.8 |
1.4 |
0.5 |
0.8 |
1.88 |
43.8 |
3050 |
0.206 |
0.443 |
210 |
175 |
205 |
| 185 |
95 |
2.0 |
1.6 |
0.5 |
0.8 |
2.04 |
48.4 |
3650 |
0.164 |
0.320 |
235 |
200 |
240 |
| 240 |
120 |
2.2 |
1.6 |
0.6 |
0.8 |
2.20 |
54.3 |
4580 |
0.125 |
0.253 |
275 |
235 |
280 |
| 300 |
150 |
2.4 |
1.8 |
0.6 |
0.8 |
2.36 |
59.7 |
5500 |
0.100 |
0.206 |
305 |
260 |
315 |
| 400 |
185 |
2.6 |
2.0 |
0.7 |
0.8 |
2.68 |
67.6 |
7000 |
0.0778 |
0.164 |
335 |
290 |
375 |
| 500 |
240 |
3.0 |
2.2 |
0.7 |
0.8 |
2.84 |
75.2 |
8600 |
0..0605 |
0.125 |
350 |
310 |
410 |
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
1.1 kv , Annealed High Conductivity solid copper conductor, 1.5 Sq. mm, pvc insulated, inner sheathed,
armoured/unarmoured pvc sheathed control cables conforming to is : 1554 (Part I) amended upto date |
| Number of cores |
Nominal thickness
of insulation |
Minimum
thickness
of
inner
sheath |
Armour |
Nominal Sheath thickness Unarm - oured |
Minimum Sheath thickness Arm - oured |
Approx. overall dlameter |
Approx. weight of cable |
Max. DC conduc - tor resistance at 20° C |
Current Ratings |
Galv.
round steel
wire
nom.
dla. |
Galv.
flat steel
strip
nom.
thick. |
Unarm - oured |
Arm - oured |
Unarm - oured |
Arm - oured |
Driect in Ground |
In Ducts |
In Air |
| |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
mm |
Kg/Km |
Kg/Km |
Ohm/Km |
Amps. |
Amps. |
Amps. |
| 2 |
0.8 |
0.3 |
1.4 |
-- |
1.80 |
1.24 |
10.20 |
13.38 |
130 |
350 |
12.1 |
23 |
20 |
20 |
| 3 |
0.8 |
0.3 |
1.4 |
-- |
1.80 |
1.24 |
10.20 |
13.38 |
160 |
400 |
12.1 |
21 |
17 |
17 |
| 4 |
0.8 |
0.3 |
1.4 |
-- |
1.80 |
1.24 |
11.50 |
14.68 |
190 |
450 |
12.1 |
21 |
17 |
17 |
| 5 |
0.8 |
0.3 |
1.4 |
-- |
1.80 |
1.24 |
12.45 |
15.55 |
225 |
500 |
12.1 |
21 |
17 |
17 |
| 6 |
0.8 |
0.3 |
1.4 |
-- |
1.80 |
1.24 |
13.20 |
16.48 |
250 |
550 |
12.1 |
15 |
13 |
13 |
| 7 |
0.8 |
0.3 |
1.4 |
-- |
1.80 |
1.24 |
13.20 |
16.48 |
265 |
565 |
12.1 |
14 |
13 |
13 |
| 10 |
0.8 |
0.3 |
1.4 |
-- |
1.80 |
1.40 |
16.20 |
18.70 |
350 |
750 |
12.1 |
13 |
11 |
11 |
| 12 |
0.8 |
0.3 |
-- |
0.8 |
1.80 |
1.24 |
17.80 |
19.20 |
400 |
650 |
12.1 |
12 |
10 |
10 |
| 14 |
0.8 |
0.3 |
-- |
0.8 |
1.80 |
1.40 |
17.90 |
19.97 |
450 |
760 |
12.1 |
11 |
10 |
10 |
| 16 |
0.8 |
0.3 |
-- |
0.8 |
1.80 |
1.40 |
19.25 |
20.87 |
500 |
800 |
12.1 |
11 |
9 |
9 |
| 19 |
0.8 |
0.3 |
-- |
0.8 |
2.00 |
1.40 |
20.00 |
21.80 |
600 |
850 |
12.1 |
10 |
9 |
9 |
| 24 |
0.8 |
0.3 |
-- |
0.8 |
2.00 |
1.40 |
23.00 |
24.90 |
725 |
1050 |
12.1 |
9 |
8 |
8 |
| 30 |
0.8 |
0.3 |
-- |
0.8 |
2.00 |
1.40 |
24.50 |
26.17 |
860 |
1200 |
12.1 |
9 |
7 |
7 |
| 37 |
0.8 |
0.3 |
-- |
0.8 |
2.00 |
1.40 |
26.00 |
28.00 |
1050 |
1400 |
12.1 |
8 |
7 |
7 |
| 61 |
0.8 |
0.3 |
-- |
0.8 |
2.00 |
1.56 |
33.00 |
34.72 |
1650 |
2100 |
12.1 |
7 |
6 |
6 |
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
1.1 kv , Annealed High Conductivity solid copper conductor, 2.5 Sq. mm, pvc insulated, inner sheathed,
armoured/unarmoured pvc sheathed control cables conforming to is : 1554 (Part I) amended upto date |
| 2 |
0.9 |
0.3 |
1.4 |
-- |
1.8 |
1.24 |
10.68 |
14.58 |
160 |
425 |
7.41 |
32 |
27 |
27 |
| 3 |
0.9 |
0.3 |
1.4 |
-- |
1.8 |
1.24 |
11.40 |
15.17 |
225 |
475 |
7.41 |
27 |
24 |
24 |
| 4 |
0.9 |
0.3 |
1.4 |
-- |
1.8 |
1.24 |
11.50 |
16.13 |
250 |
530 |
7.41 |
27 |
24 |
24 |
| 5 |
0.9 |
0.3 |
1.4 |
-- |
1.8 |
1.24 |
14.10 |
17.49 |
300 |
600 |
7.41 |
27 |
24 |
24 |
| 6 |
0.9 |
0.3 |
1.4 |
-- |
1.8 |
1.24 |
15.40 |
18.28 |
340 |
675 |
7.41 |
20 |
18 |
18 |
| 7 |
0.9 |
0.3 |
1.4 |
-- |
1.8 |
1.24 |
15.40 |
18.28 |
375 |
700 |
7.41 |
20 |
17 |
17 |
| 10 |
0.9 |
0.3 |
-- |
0.8 |
1.8 |
1.40 |
19.00 |
21.10 |
500 |
780 |
7.41 |
18 |
15 |
15 |
| 12 |
0.9 |
0.3 |
-- |
0.8 |
2.0 |
1.40 |
20.00 |
21.69 |
600 |
850 |
7.41 |
17 |
14 |
14 |
| 14 |
0.9 |
0.3 |
-- |
0.8 |
2.0 |
1.40 |
20.90 |
22.62 |
650 |
950 |
7.41 |
16 |
13 |
13 |
| 16 |
0.9 |
0.3 |
-- |
0.8 |
2.0 |
1.40 |
22.10 |
23.69 |
750 |
1050 |
7.41 |
15 |
13 |
13 |
| 19 |
0.9 |
0.3 |
-- |
0.8 |
2.0 |
1.40 |
23.00 |
24.80 |
850 |
1150 |
7.41 |
14 |
12 |
12 |
| 24 |
0.9 |
0.3 |
-- |
0.8 |
2.0 |
1.40 |
26.60 |
28.82 |
1050 |
1400 |
7.41 |
13 |
11 |
11 |
| 30 |
0.9 |
0.3 |
-- |
0.8 |
2.0 |
1.56 |
28.40 |
30.34 |
1250 |
1700 |
7.41 |
12 |
10 |
10 |
| 37 |
0.9 |
0.4 |
-- |
0.8 |
2.2 |
1.56 |
31.00 |
32.72 |
1550 |
2000 |
7.41 |
11 |
10 |
10 |
| 61 |
0.9 |
0.4 |
-- |
0.8 |
2.2 |
1.56 |
38.40 |
40.44 |
2450 |
3100 |
7.41 |
9 |
8 |
8 |
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
| conductor resistance of plain copper conductors used for heavy duty cables as per is:8130-1984 |
| Size in sq. mm |
Conductor Construction |
Max. cond. resistance in ohm /km at 20°C in |
Size in sq. mm |
Conductor Construction |
Max. cond. resistance in ohm /km at 20°C in |
| Single core & Multi core |
Single core & Multi core |
| 1.5* |
1/1.38 |
12.100 |
120 |
37/2.03 |
0.153 |
| 1.5* |
1/1.78 |
7.410 |
150 |
37/2.24 |
1.124 |
| 4.0* |
1/2.24 |
4.610 |
185 |
37/2.50 |
0.0991 |
| 6.0* |
1/2.76 |
3.080 |
240 |
61/2.24 |
0.0754 |
| 10 |
7/1.35 |
1.830 |
300 |
61/2.50 |
0.0601 |
| 16 |
7/1.70 |
1.150 |
400 |
61/2.85 |
0.0470 |
| 25 |
7/2.14 |
0.727 |
500 |
61/3.20 |
0.0366 |
| 35 |
7/2.50 |
0.524 |
630 |
91/3.00 |
0.0283 |
| 50 |
7/3.00 |
0.387 |
-- |
-- |
-- |
| 70 |
19/2.14 |
0.268 |
800 |
127/2.83 |
0.0221 |
| 95 |
19/2.50 |
0.193 |
1000 |
127/3.16 |
0.0176 |
---------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------------
| current rating of “polycab” copper armoured/unarmoured cables 650/1100 v Grade in Air |
| Area Sq.mm |
Twin Core Amp. |
3, 31/2 , 4 Core Amp. |
Area Sq.mm |
Twin Core Amp. |
3, 31/2 , 4 Core Amp. |
| 1.5 |
20 |
17 |
70 |
195 |
165 |
| 2.5 |
27 |
24 |
95 |
230 |
200 |
| 4 |
35 |
30 |
120 |
265 |
235 |
| 6 |
45 |
39 |
150 |
305 |
265 |
| 10 |
60 |
52 |
185 |
350 |
305 |
| 16 |
78 |
66 |
240 |
410 |
355 |
| 25 |
105 |
90 |
300 |
465 |
400 |
| 35 |
125 |
110 |
400 |
530 |
455 |
| 50 |
155 |
135 |
-- |
-- |
-- |
|
|
|